The HazenâÂÂWilliams equation is an empirical relationship that relates the flow of water in a pipe with the physical properties of the pipe and the pressure drop caused by friction. It is used in the design of water pipe systems such as fire sprinkler systems, water supply networks, and irrigation systems. It is named after Allen Hazen and Gardner Stewart Williams.
The HazenâÂÂWilliams equation has the advantage that the coefficient C is not a function of the Reynolds number, but it has the disadvantage that it is only valid for water. Also, it does not account for the temperature or viscosity of the water, and therefore is only valid at room temperature and conventional velocities.
Henri Pitot discovered that the velocity of a fluid was proportional to the square root of its head in the early 18th century. It takes energy to push a fluid through a pipe, and Antoine de Chézy discovered that the hydraulic head loss was proportional to the velocity squared. Consequently, the Chézy formula relates hydraulic slope S (head loss per unit length) to the fluid velocity V and hydraulic radius R:
The variable C expresses the proportionality, but the value of C is not a constant. In 1838 and 1839, Gotthilf Hagen and Jean Léonard Marie Poiseuille independently determined a head loss equation for laminar flow, the HagenâÂÂPoiseuille equation. Around 1845, Julius Weisbach and Henry Darcy developed the DarcyâÂÂWeisbach equation.
The Darcy-Weisbach equation was difficult to use because the friction factor was difficult to estimate. In 1906, Hazen and Williams provided an empirical formula that was easy to use. The general form of the equation relates the mean velocity of water in a pipe with the geometric properties of the pipe and the slope of the energy line.
where:
The equation is similar to the Chézy formula but the exponents have been adjusted to better fit data from typical engineering situations. A result of adjusting the exponents is that the value of C appears more like a constant over a wide range of the other parameters.
The conversion factor k was chosen so that the values for C were the same as in the Chézy formula for the typical hydraulic slope of S=0.001. The value of k is 0.001<sup>âÂÂ0.04</sup>.
Typical C factors used in design, which take into account some increase in roughness as pipe ages are as follows:
The general form can be specialized for full pipe flows. Taking the general form
and exponentiating each side by gives (rounding exponents to 3âÂÂ4 decimals)
Rearranging gives
The flow rate , so
The hydraulic radius (which is different from the geometric radius ) for a full pipe of geometric diameter is ; the pipe's cross sectional area is , so
When used to calculate the pressure drop using the US customary units system, the equation is:
where:
When used to calculate the head loss with the International System of Units, the equation will then become
where: